- ON/OFF control and dimming of individual or grouped luminaires
- Selection of PWM output frequency by ETS, from 250 Hz to 6 kHz
- Parallel connection of outputs possible to increase output power
- Fade on/off time, minimum and maximum brightness level, linear or logarithmic dimming curve settable via ETS
- Soft or instantaneous switching on and off, with settable delay
- Configuration of behaviour after power reset, bus ON/OFF, unloading via ETS
- Channels can be set by ETS as independent, parallel or with copy function from another channel
- Blocking function, forced operation, staircase light, scenes, night, counter and logic functions for each channel, settable from ETS
- Alarm for power failure
- Manual control with membrane buttons for local ON/OFF testing of channels 1-2-3-4: in manual mode, short press of a channel button activates/deactivates the load, pressing for at least 2 seconds causes the load to flash every 1 s approx.
- Relay contact for switching off the AC/DC power supply when 12/24/48 Vdc outputs are switched off, or alternatively as relay for auxiliary output
- Auxiliary output function via relay with status indication via KNX
Environmental conditions and other features
- Operating temperature: -20 °C ... + 40 °C
- Storage temperature: -40 °C ... + 60 °C
- Transport temperature: -40 °C ... + 60 °C
- Max. nominal enclosure temperature (tc): 80 °C
- Relative humidity: 91% non-condensing
- Degree of protection: IP00 (IP20 in junction box or switchboard)
- Power supply and load wiring: 0.2 to 4.0 mm2 (24 to 11 AWG) for single cable / 0.2 to 6 mm2 (24 to 9 AWG) for stranded cable
- KNX bus wiring: 0.6 to 0.8 mm2 (19 to 18 AWG)
- Stripping: 8.0 mm
- Plastic housing
- Switchgear for panel mounting on 4 UM DIN rail
- Weight: 200 g
- Dimensions (WxHxD): 71 x 91 x 62 mm